1 3690 N.W. 53rd Street Fort Lauderdale, FL 33309 SC-2124 SC-2124M 24 Channel Universal Scanner Installation and Operation Manual P/N 1

Strona 2

102.2 Wiring (Cont’d) Connectors D and E are input terminals, each requiring p/n SC-CBLE25MM cable / terminal block assembly. Thermocouples can be

Strona 3 - 1.0 Introduction

11 Connector E (DB-25F) This Connector provides the Analog Inputs for Channels 13 – 24. Pinout: Pin# Pin Name Pin# Pin Name 1 Channel 1

Strona 4 - Front View

122.2 Wiring (Cont’d) Optional DB cables and DB-to-Screw -Terminal DIN-RAIL Modules are available CONN

Strona 5

133.0 Setup The SC-2124 requires the user to configure a variety of parameters: SCANNER channel analog inputs; ALARM & SHUTDOWN TRIP conditions;

Strona 6 - 1.2 Specifications

143.1.1 Setup Screen The SCANNER has the capability of communicating via Dynalink (point to point) using the communications cable p/n CBLE-8509 or v

Strona 7 - 2.1 Panel Cutout

15 3.1.2 Configuration File The easiest method for the user to configure the SC-2124 is by editing and downloading a configuration file to the SCANN

Strona 8 - 2.2 Wiring

164.0 Standard Operation After power-up, the SC-2124 performs all standard SCANNER operations continually. These operations include scanning all en

Strona 9

174.1 RESET After power-up, the SC-2124 starts up in a RESET condition that assumes that all channels are in a non-fault state, initializes the ALAR

Strona 10 - 2.2 Wiring (Cont’d)

184.3 ALARM The SCANNER provides a precautionary ALARM warning to alert the user to potentially hazardous or dangerous input conditions. The SCANNE

Strona 11

195.0 User Interface The SC-2124 user interface located on the front panel of the SCANNER consists of a large-character, 4-row by 20-column, backlit

Strona 12 - CONN ACONN CCONN E CONN D

2TABLE OF CONTENTS 1.0 Introduction 3 1.1 Ratings & Certification 6 2.0 Installation 7 2.

Strona 13 - 3.1 HOST Software

20 Figure 2, Run Screens DYNALCO CONTROLS SCAN-2124 V1.00 0 10 - + MAIN SCAN CUSTOM CH SNAP 10 0100 200 110 120SCN CH01 ENG

Strona 14 - SETUP SCREEN

215.2 Run Screens The main purpose of the SC-2124 Run Screens is to allow the user to navigate to and from screens that display current run-time val

Strona 15 - 3.1.2 Configuration File

22After startup, the user may navigate to the Title Screen from the Main Menu Screen. This allows the user to adjust the LCD contrast at any time du

Strona 16 - 4.0 Standard Operation

235.2.4 SCAN Screen The SCAN Screen is the default SCANNER screen. The SCAN Screen displays each enabled scanner channel for three seconds (delay i

Strona 17 - 4.2 START

245.2.6.1 HELP Screens In addition to viewing the channel’s current analog input reading, the Channel Screen provides a link to channel HELP Screens

Strona 18 - 4.4 SHUTDOWN

25 Appendix A This appendix contains a table of all parameter numbers found in the SCAN2124.SPC file. Use this appendix to keep track of the values

Strona 19 - 5.1 Navigation

26Scan Screen Settings Parameter Description Valid Inputs 195= Selects type of scan screen to view (default or 0= displays default screen (enabled

Strona 20 - SCAN-2124 Run Screens

27Channel 1 Input Settings Parameter Function Description Valid Inputs 110.1= Channel name for CH01 Default=” “ (blank=CH01) 11 characters (inclu

Strona 21 - 5.2.1 Title Screen

28Channel 2 Input Settings Parameter Function Description Valid Inputs 110.2= Channel name for CH02 Default=” “ (blank=CH02) 11 characters (inclu

Strona 22 - 5.2.3 Main SCANNER Screen

29Appendix C Channel 3 Input Settings Parameter Function Description Valid Inputs 110.3= Channel name for CH03 Default=” “ (blank=CH03) 11 charac

Strona 23 - 5.2.6 Channel Screens

31.0 Introduction The SC-2124 is a microprocessor-based universal scanner for continuous monitoring of up to 24 channels measuring temperature from

Strona 24 - 5.2.7.1 First-Out Screen

30Channel 4 Input Settings Parameter Function Description Valid Inputs 110.4= Channel name for CH04 Default=” “ (blank=CH04) 11 characters (inclu

Strona 25 - Appendix A

31Appendix C Channel 5 Input Settings Parameter Function Description Valid Inputs 110.5= Channel name for CH05 Default=” “ (blank=CH05) 11 charac

Strona 26

32Channel 6 Input Settings Parameter Function Description Valid Inputs 110.6= Channel name for CH06 Default=” “ (blank=CH06) 11 characters (inclu

Strona 27 - Minimum=-1000.0

33Appendix C Channel 7 Input Settings Parameter Function Description Valid Inputs 110.7= Channel name for CH07 Default=” “ (blank=CH07) 11 charac

Strona 28

34Channel 8 Input Settings Parameter Function Description Valid Inputs 110.8= Channel name for CH08 Default=” “ (blank=CH08) 11 characters (inclu

Strona 29 - Appendix C

35Appendix C Channel 9 Input Settings Parameter Function Description Valid Inputs 110.9= Channel name for CH09 Default=” “ (blank=CH09) 11 charac

Strona 30

36Channel 10 Input Settings Parameter Function Description Valid Inputs 110.10= Channel name for CH10 Default=” “ (blank=CH10) 11 characters (inc

Strona 31

37Appendix C Channel 11 Input Settings Parameter Function Description Valid Inputs 110.11= Channel name for CH 11 Default=” “ (blank=CH11) 11 cha

Strona 32

38Channel 12 Input Settings Parameter Function Description Valid Inputs 110.12= Channel name for CH12 Default=” “ (blank=CH12) 11 characters (inc

Strona 33

39Appendix C Channel 13 Input Settings Parameter Function Description Valid Inputs 110.13= Channel name for CH13 Default=” “ (blank=CH13) 11 char

Strona 34

41.1 Packaging Front View 6.55"8.50"

Strona 35

40Channel 14 Input Settings Parameter Function Description Valid Inputs 110.14= Channel name for CH14 Default=” “ (blank=CH14) 11 characters (inc

Strona 36

41Appendix C Channel 15 Input Settings Parameter Function Description Valid Inputs 110.15= Channel name for CH15 Default=” “ (blank=CH15) 11 char

Strona 37

42Channel 16 Input Settings Parameter Function Description Valid Inputs 110.16= Channel name for CH16 Default=” “ (blank=CH16) 11 characters (inc

Strona 38

43Appendix C Channel 17 Input Settings Parameter Function Description Valid Inputs 110.17= Channel name for CH17 Default=” “ (blank=CH17) 11 char

Strona 39

44Channel 18 Input Settings Parameter Function Description Valid Inputs 110.18= Channel name for CH18 Default=” “ (blank=CH18) 11 characters (inc

Strona 40

45Appendix C Channel 19 Input Settings Parameter Function Description Valid Inputs 110.19= Channel name for CH19 Default=” “ (blank=CH19) 11 char

Strona 41

46Channel 20 Input Settings Parameter Function Description Valid Inputs 110.20= Channel name for CH20 Default=” “ (blank=CH20) 11 characters (inc

Strona 42

47Appendix C Channel 21 Input Settings Parameter Function Description Valid Inputs 110.21= Channel name for CH21 Default=” “ (blank=CH21) 11 char

Strona 43

48Channel 22 Input Settings Parameter Function Description Valid Inputs 110.22= Channel name for CH22 Default=” “ (blank=CH22) 11 characters (inc

Strona 44

49Appendix C Channel 23 Input Settings Parameter Function Description Valid Inputs 110.23= Channel name for CH23 Default=” “ (blank=CH23) 11 char

Strona 45

5Rear View CONN ECONN DCONN ACONN CANALOGINPUTS 1-12RELAYCONTACTS (1) RLY 1 N/C (3) RLY 1 COM. (5) RLY 1 N/O (7) RLY 2 N/C (9) RLY 2

Strona 46

50Channel 24 Input Settings Parameter Function Description Valid Inputs 110.24= Channel name for CH24 Default=” “ (blank=CH24) 11 characters (inc

Strona 47

51Appendix C User-defined Trips User Trip Class Parameter Define the trip class for: Valid Inputs 63000.49= user trip 01 0=Class A over (defaul

Strona 48

52User Trip Timer Valid Inputs Parameter Sets the delay time between: 63003.49= exceeded user trip 01 threshold and channel fault63003.50= exceed

Strona 49

53Appendix C Meter Channel Sources Sets the channel to view on: Valid inputs: 0 = off (default) 1 to 24= analog input channel

Strona 50

53APPENDIX B. Example of a Configuration File (SCAN2124.SPC) ;***************************************************************************** ;

Strona 51

54/*$PAGE*/ ; ************** SCAN SCREEN ************** ; Main SCANNER Screen. ; 0 (dflt) SCAN screen displays all ; ENABLED

Strona 52 - User Relay Assignment

55/*$PAGE*/ ; ************ AI DELAY TIMERS ************ ; CHANNEL READ DLY TIME ******************* ; Dly time between analog sw setup & analo

Strona 53

56 /*$PAGE*/ ; ************ AI CHANNEL #01 ************* ; <ANALOG INPUT CHANNEL #01> ; AI CH NAME ****************************** ; User-def

Strona 54 - APPENDIX B

57 ; AI CH FILTER CONSTANT ******************* ; Averages new AI readings into current AI ; value by the following equation: ; ; AI = [AI_prev

Strona 55

58/*$PAGE*/ ; AI CH ALARM & SHUTDOWN TRIP CLASS ******* ; 0 Off (dflt) ; 1 Class A Over ; 2 Class B Over ;

Strona 56

6 1.2 Specifications 1. Input Channels:24 Thermocouple (J,K,T, or E), 0 – 5V, or 4 – 20mA (On-Board 100 Ohm resistor provided on Channels 1 thro

Strona 57

59/*$PAGE*/ ; ************ AI CHANNEL #02 ************* ; <ANALOG INPUT CHANNEL #02> ; AI CH NAME ****************************** ; User-defi

Strona 58

60 ; AI CH FILTER CONSTANT ******************* ; Averages new AI readings into current AI ; value by the following equation: ; ; AI = [AI_prev

Strona 59

61/*$PAGE*/ ; AI CH ALARM & SHUTDOWN TRIP CLASS ******* ; 0 Off (dflt) ; 1 Class A Over ; 2 C

Strona 60

62/*$PAGE*/ ; ************** USER TRIPS *************** ; USER-defined TRIPs allow mapping from ; any Analog Input channels (or RPM input) ; to

Strona 61

6363001.58=0 ; <USER TRIP #10> ; USER TRIP HYS *************************** ; TRIP hysteresis; difference between fault ; threshold o

Strona 62

64/*$PAGE*/ ; USER TRIP SOURCE ************************ ; 0 OFF (dflt) ; 1-24 AI Channels ; 25 RPM 121.1=0 ; <USER TRIP #

Strona 63

65/*$PAGE*/ ; *************** RPM TRIPS *************** ; !!!!!! Only if RPM Input available !!!!!! ; ***************************************** ; R

Strona 64

66/*$PAGE*/ ; ************* METER MODULE ************** ; !!! Only if Digital METERs available !!!! ; ***************************************** ; **

Strona 65

67APPENDIX C Instructions for Downloading WinHost from Dynalco website: 1. Go to the www.Dynalco.com web site. Start by clicking on the “Support”

Strona 66

68APPENDIX D Modbus Addresses (SC-2124M Only) These addresses are all RUN time related (Function Code 03) RANGE CHANNELS VALUE INTEGER D

Strona 67

72.0 Installation Installation requires a cutout as shown in section 2.1 along with four mounting holes. Once the unit is mounted, a nearby (less

Strona 68 - APPENDIX C

69APPENDIX E Instructions for SC-RTD configuration: The SC-RTD module is required for any inputs to be configured for RTD type inputs. Each module

Strona 69 - APPENDIX D

8 2.2 Wiring Connector A (DB-15M): This Connector is used for the DC Power Input and the Cold Junction Compensation (CJC) Sensor Input. In additi

Strona 70 - APPENDIX E

92.2 Wiring (Cont’d) Connector C (DB-25M) This Connector provides Contact Outputs for the 4 on-board relays. Pinout: Pin# Pin Name 1 Relay 1 NC